FAQs Single template
- Select PM channel
The AIR XD has 2 x 4 mA to 20 mA outputs that can be assigned to one of four particulate sizes or TSP. To select the channel go to Settings > 4-20mA > Channel 1 > PM Channel and then select the PM value. - Map 4 mA to 20mA to data channel
Map the selected 4 mA to 20 mA output to the required data channel (“Live”, “Average 1” or “Average 2”). To map the data channel go to, Settings > 4-20mA > Channel 1 > Data Channel and then select the option you require. - Set maximum PM value
Set the 4 mA to 20 mA scaling range for each 4 mA to 20 mA output. (0 to 9,999 μg/m3 or 0.1 to 6,553 mg/m3. To set the maximum PM value go to Settings > 4-20mA > Channel 1 > Max PM and then set the value. -
Enable/Disable
Enable or disable 4 mA to 20 mA outputs. To enable or disable the 4 mA to 20mA output go to Settings > 4-20mA > Channel 1 > En/Dis and then select the option. -
Check Status
Check the overview status of the 4 mA to 20 mA channels. To check the status of the 4 mA to 20mA outputs go to Settings > 4-20mA > Status.