FAQs Single template

  1. Select the appropriate Channel
    AIR XD has 2 x alarm channels that can be assigned one of four particulate sizes or TSP. To select the appropriate channel, go to SettingsAlarmsAlarm 1Channel Select and select the PM size that you want to monitor.
  2. Select the Threshold Channel
    Select and assign an alarm to a specified data source. To select the data source, go to Settings > Alarms > Alarm 1 > Channel Select and select the PM size that you want to monitor.
  3. Set Alarm Threshold
    Set the threshold value, which activates the alarm. Threshold values can be configured between 1 μg/m3 to 9,999 μg/m3 or 0.1 mg/m3 to 6,553.5 mg/m3. To set the threshold, go to Settings > Alarms > Alarm 1 > Set Threshold and select enter the value of the threshold.

  4. Set Alarm Latching
    Configure the latching behaviour for the selected alarm. To set the alarm latching, go to SettingsAlarmsAlarm 1Latching En/Dis and select whether you want to enable or disable latching.
  5. Enable/Disable the Alarm
    Enable to disable audio-visual alarms for selected alarm. To enable or disable the alarm, go to SettingsAlarmsAlarm 1Enable/Disable and select whether you want to enable or disable.